Motor Winding Temperature Classes Explained

By Qin Chen | 6 Nov 2026

A motor nameplate shows an insulation class, often F, and many people read it as the temperature the motor runs at. It is not.

Class and rise are different

An IEEE presentation on motors states that temperature rise and insulation class are two different things. The temperature rise depends on the winding design and the motor's ability to remove heat. The insulation class is the thermal capability of the insulation system. The class of a motor's insulation system can be changed to a higher or lower class without affecting the temperature rise.

The classes

The same source gives the class limits as the maximum hot-spot temperature at which the insulation system can be operated for its normal expected service life:

  • Class B: 130 C
  • Class F: 155 C
  • Class H: 180 C

Class A is lower; the same slide shows it at a 55 C rise in its example. For the wire side of thermal class, see thermal class of magnet wire.

Temperature rise limits in NEMA MG 1

NEMA MG 1 Part 12 gives temperature rise limits for small and universal motors by class, based on a maximum ambient temperature of 40 C. For windings of open motors, measured by resistance or thermocouple, the limits are 60 C for class A, 80 C for B, 105 C for F and 125 C for H. For totally enclosed fan-cooled motors they are 65, 85, 110 and 135 C. The standard notes that where class F or H is used, special consideration should be given to bearing temperatures and lubrication, and that abnormal deterioration of insulation may be expected if the 40 C ambient is exceeded in regular operation. It also notes that the rise values assume altitude of 1000 m or less. These tables are for small and universal motors; other motor types have their own tables in the standard.

Hot spot and life

The IEEE presentation shows the total winding temperature as ambient plus rise plus a hot-spot allowance, with 10 C for the hot spot in its example. It gives a rule of thumb that a 10 C increase in temperature halves the life of the insulation system. Use it as an indication, not a prediction.

What to check

  1. Class on the nameplate and ambient limit.
  2. Measured winding temperature rise, by resistance. See motor winding resistance testing.
  3. Altitude and cooling.
  4. Duty: starts, overloads and variable speed.
  5. The wire's own class. See thermal class of magnet wire.

Frequently asked questions

Does class F mean the motor runs at 155 C?

No. Class F is the hot-spot capability of the insulation system. The temperature rise depends on the design and cooling.

What are the class temperatures?

B 130 C, F 155 C and H 180 C maximum hot spot, per an IEEE presentation.

What ambient do the tables assume?

40 C.

Can a motor with class F insulation have a class B rise?

Yes, class and rise are independent. Many motors have class F with lower rise to give margin.

What does 10 C do to life?

A rule of thumb says it halves insulation life.