Motor Winding Resistance Testing: Methods and Interpretation
A motor can pass an insulation test and still have a loose lug, a cracked strand or a few shorted turns. Winding resistance testing looks at the copper path itself. It measures the DC resistance of each winding and compares phases with each other and with earlier values. This guide covers how it is done and how to read the result.
Only qualified people should test windings. Disconnect the motor from its supply, lock out and verify it is dead, and follow the manufacturer's instructions and the site's safety rules. Windings and cables can hold charge after other tests so discharge and ground them as the test equipment maker directs before connecting or removing leads.
What the test measures
The test passes a known DC current through a winding and measures the voltage drop, then applies Ohm's law. Motor windings can be a fraction of an ohm, so an ordinary multimeter is often not accurate enough. It checks the conductor, not the insulation.
What it can find
- Resistive connections, inside or outside the machine, such as a loose or corroded terminal or a poor joint.
- Open or partly broken strands in coils wound with several wires in parallel.
- Open or shorted coils, and wrong turn count or wire gauge.
- Incorrect coil or group connections.
It does not replace other tests. Some faults show on a resistance test and not on a surge test: for example, if two of four parallel wires in a coil are broken, the inductance may not change, so a surge test can miss it, while the resistance rises. The reverse also holds, so the tests complement each other. See our article on surge testing and on common winding failures.
Use four-wire measurement
With a two-wire meter, the leads and clamp contacts add their own resistance, which can be as large as the winding itself. The four-wire, or Kelvin, method uses one pair of leads to carry the test current and a separate pair to sense the voltage right at the winding. Almost no current flows in the sense leads, so their resistance does not affect the reading. It is the recommended approach for low resistances. Use the same test points each time.
Compare phases
On a three-phase motor, measure each phase path, for example between T1 and T2, T2 and T3, and T3 and T1, and compare the three readings. In a healthy motor the phases are wound the same way, so readings should be close, and the relationship between them often tells you more than the absolute value. Readings of 0.284, 0.283 and 0.285 ohm are consistent. A third reading of 0.320 ohm needs investigation.
A higher reading can come from a loose terminal, corrosion, a damaged conductor or a poor splice. A lower reading can come from bypassed turns. The test shows that a phase differs, not why.
How imbalance is calculated
One test-equipment maker, Electrom Instruments, gives the balance as a percentage: (R max minus R min) divided by R average, where R max and R min are the highest and lowest of the three phase-to-phase readings and R average is their mean. Note this is the spread between the highest and lowest reading over the mean, which is not the same as the largest deviation of one reading from the mean. If you quote a figure, state which method was used. Resistance imbalance is also a different quantity from supply voltage or current unbalance, which describe the supply and the motor response to it. Do not apply limits for one to the other.
This article gives no pass or fail percentage. Published figures vary by source, method and machine, and we could not confirm a universal acceptance limit from the standard itself. Use the motor manufacturer's criteria, the factory test report, or the repair specification, and your own earlier readings of the same motor.
Winding connection matters. Depending on the lead configuration, a reading between two terminals may pass through one winding or through more than one path, so the expected value differs. Compare against manufacturer data for that connection, measured the same way each time.
Temperature
Copper resistance rises with temperature, so the same healthy winding reads higher when warm. Record the winding temperature with every reading. To compare readings over time or against a report, test at the same temperature or correct to the reference temperature the report uses, with the correction procedure from the instrument or motor manufacturer. For copper, the correction constant depends on the conductor material, so do not use a generic figure.
Because the balance calculation is a ratio of readings taken together, one test-equipment maker notes that temperature compensation is not needed for phase balance alone, provided all three phases are at the same temperature.
Trend over time
A single reading is a snapshot. Readings taken at the same points, at the same temperature, over time show a connection that is slowly deteriorating long before it fails. Test the same way each time, since installed cables add their own resistance.
Frequently asked questions
Why not use a normal multimeter?
Motor windings can be a fraction of an ohm, and lead and contact resistance can be as large as the winding. A low-resistance ohmmeter with four-wire measurement avoids that error.
What does an unbalanced winding resistance mean?
One phase presents a different path from the others. Causes include a loose connection, damaged conductor or poor joint (higher reading) or bypassed turns (lower reading). It calls for further investigation.
What balance is acceptable?
It depends on the motor, the connection and the specification. Published limits vary and we found no universal figure. Use the manufacturer criteria, the factory report or earlier tests of the same motor.
Does temperature matter?
Yes. Resistance rises as the winding warms, so record temperature and compare at the same temperature or correct using the manufacturer procedure.